Convert the current signal from the safe area into a 4mA to 20mA current signal through isolation and output it to the hazardous area. On site equipment such as electrical converters and valve positioners that can control hazardous areas. The three terminal isolation of input, output, and power supply has the advantages of fast response, low power consumption, and good temperature characteristics.
2、 Technical parameters
Explosion proof mark: Exia]ⅡC
Dangerous area allows output signal: current signal
Can input signal to the safe zone: 4mA~20mA
Output load capacity: ≤ 500 Ω; If larger load capacity is required, please customize
Output ripple:< 1mV
Isolation transmission accuracy: ± 0.2% F ∙ S (25 ℃± 2 ℃)
Temperature drift:< 30ppm/℃
Response time: ≤ 0.2ms
Stability time: ≤ 2ms
Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, test time 1min)
Insulation resistance: ≥ 100M Ω (between input/output/power supply)
Electromagnetic compatibility: EMC complies with IEC61000-4
Certification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST): Um=250V AC/DC

9. Between 10 terminals: Uo=25.2V,Io=85mA,Po=536mW
ⅡC ⅡB ⅡA
Co 0.074μF 0.57μF 2.03μF
Lo 3.4mH 10.2mH 27.2mH
Power supply: DC 18-32V (typical value 24V DC)
Power consumption: 0.4W
3、 Precautions
The installation location must not have strong vibrations, as well as electromagnetic interference from signal terminals, power terminals, and space exceeding the third category of industrial site electromagnetic interference in the IEC61000-4 series, and there must be no harmful substances in the environment that can cause serious corrosion to metal and plastic parts.
4、 Usage environment
Working environment temperature: - 20℃~+60℃
Allowable relative humidity at work: 10% RH to 90% RH (40 ℃)
Allowable atmospheric pressure during work: 80kPa~106kPa
Allowable ambient temperature during storage and transportation: - 40℃~+80℃
5、 Panel indicator light
PWR: The green power indicator light is always on when the instrument is working normally.
RELATED
RELATED
RELATED
RELATED
Company Address:
Building 5 and 11, Fuzhou IoT Industrial Park,
No. 12 Xingye West Road, Mawei District,
Fuzhou City, Fujian Province, China
Market Cooperation:
Manager Guo: 13959146212
Copyright © 2025 Fujian Aotai Automation Equipment Co., Ltd
This website uses cookies to ensure you get the best experience on our website.
Comment
(0)