Login | Register
产品中心
Home > Product > Rail mounted instruments > AO5062 detection terminal voltage input isolated safety barrier (two in, two out)

AO5062 detection terminal voltage input isolated safety barrier (two in, two out)

    AO5062 detection terminal voltage input isolated safety barrier (two in, two out)

  • Category:
    Rail mounted instruments
  • Browse number:
    462
  • Release time:
    2025-05-07 16:08:19
  • Share:
  • INQUIRY

1、 Performance Overview


Convert the voltage signal from the danger zone into a current/voltage signal through isolation and output it to the safe zone. The three terminal isolation of input, output, and power supply has the advantages of fast response, low power consumption, and good temperature characteristics.


电流输入隔离式安全栅


2、 Technical parameters


Explosion proof mark: [Exia] IIC


Dangerous area allows input signal: voltage signal


Input impedance: ≥ 1MΩ


Signal frequency range: 0Hz~300Hz (customizable within the range of 0Hz~5kHz)


Can output signals to the safe zone:


Current: 0 (4) mA~20mA; 0mA~10mA;


Voltage: 0 (1) V to 5V; 0V~10V;


Load capacity:


Current: 0 (4) mA~20mA: ≤ 300 Ω; 0mA~10mA: ≤ 600Ω


Voltage: 0 (1) V~5V: ≥ 1M Ω; 0V~10V: ≥ 2MΩ


Distribution output voltage: open circuit voltage ≤ 18V,


Voltage ≥ 14.5V at full load 20mA output


Output ripple:< 1mV temperature drift:< 30ppm/℃


Isolation transmission accuracy: ± 0.2% F ∙ S (25 ℃± 2 ℃)


Response time: ≤ 0.2ms stabilization time: ≤ 2ms


Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, test time 1min)


Insulation resistance: ≥ 100M Ω (between input/output/power supply)


Electromagnetic compatibility: EMC complies with IEC61000-4


Certification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST): Um=250V AC/DC


10. Between terminals 11, between terminals 14 and 15: Uo=13.7V,Io=3mA,Po=10.3mW


ⅡC           ⅡB          ⅡA


Co        0.553μF       3.50μF      12.6μF


Lo        1000mH        1000mH      1000mH


9. Between terminals 11, between terminals 13 and 15: Uo=21V,Io=125mA,Po=657mW


ⅡC           ⅡB      ⅡA


Co        0.13μF        0.89μF   3.34μF


Lo        1.59mH        4.77mH   12.72mH


Power supply: DC 18-32V (typical value 24V DC)


Power consumption: 24V DC power supply, dual output 1.6W


3、 Panel indicator light


PWR: The green power indicator light is always on when the instrument is working normally;


4、 Usage environment


Working environment temperature: - 20℃~+60℃


Allowable relative humidity at work: 10% RH to 90% RH (40 ℃)


Allowable atmospheric pressure during work: 80kPa~106kPa


Allowable ambient temperature during storage and transportation: - 40℃~+80℃


5、 Precautions


The installation location must not have strong vibrations, as well as electromagnetic interference from signal terminals, power terminals, and space exceeding the third category of industrial site electromagnetic interference in the IEC61000-4 series, and there must be no harmful substances in the environment that can cause serious corrosion to metal and plastic parts.


    


ONLINE MESSAGE

*Subject:
*E-mail:
Phone:
Company:
*Captcha:

RELATED PRODUCTS

Contact Us

Company Address:

Building 5 and 11, Fuzhou IoT Industrial Park, 

No. 12 Xingye West Road, Mawei District, 

Fuzhou City, Fujian Province, China

Market Cooperation:

Manager Guo: 13959146212


Copyright © 2025 Fujian Aotai Automation Equipment Co., Ltd

This website uses cookies to ensure you get the best experience on our website.

Accept Reject