Login | Register
产品中心
Home > Product > Rail mounted instruments > AO5922 detection end thermocouple input isolation safety barrier (two in, two out)

AO5922 detection end thermocouple input isolation safety barrier (two in, two out)

    AO5922 detection end thermocouple input isolation safety barrier (two in, two out)

  • Category:
    Rail mounted instruments
  • Browse number:
    642
  • Release time:
    2025-05-07 16:46:35
  • Share:
  • INQUIRY

1、 Performance Overview


Isolate and convert thermocouple signals from hazardous areas into current/voltage signals for safe areas, automatically compensating for cold junction temperature. The input end, output end, and power supply end are three terminal isolated, with functions such as online fault self diagnosis, making it an intelligent safety barrier product. Optional use of our company's dedicated handheld programmer for parameter modification or calibration (see Programmer User Manual for details).


2、 Technical parameters


Explosion proof grade: [Exia] IIC


Dangerous area allows input signals:


Thermocouples (K, E, S, B, J, T, R, N, WRe3-WRE25, WRe5-WRe26);


The signal type and range are determined at the time of ordering and can also be programmed by oneself.


Output signal to the safe zone:


Current: 0 (4) mA~20mA;    0mA~10mA;


Voltage: 0 (1) V to 5V;       0V~10V;


Please specify other output signal types when placing an order.


热电偶输入隔离式安全栅


Output load capacity:


Current: 0 (4) mA~20mA: ≤ 300 Ω; 0mA~10mA: ≤ 600 Ω


Voltage: 0 (1) V~5V: ≥ 1M Ω; 0V~10V: ≥ 2M Ω


Isolation transmission accuracy: ± 0.2% F · S (25 ℃± 2 ℃ excluding cold end compensation)


Response time: 2s Temperature drift:<30ppm/℃


Cold end temperature compensation accuracy: ± 2 ℃ (preheating for 10 minutes)


Cold end temperature compensation range: -20 ℃ to+60 ℃


Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, testing time 1min)


Insulation resistance: ≥ 100M Ω (between input/output/power supply)


Electromagnetic compatibility: EMC complies with IEC61000-4


Certification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST): Um=250V AC/DC


10. Between terminals 11, between terminals 14 and 15:


Uo=6.5V,Io=9.7mA,Po=15.8mW


ⅡC           ⅡB         ⅡA


Co        17.5μF        399μF       700μF


Lo        264mH         792mH       1000mH


Power supply: DC 18-32V (typical value 24V DC)


Power consumption: DC 24V power supply 0.6W


3、 Output status during input fault


Follow method: Unless otherwise specified by the user, regardless of the fault state of the input signal (open circuit, short circuit, reverse connection, over range), the output will follow the changes of the input signal within the full range, but not exceed 12.5% of the output range (for example, when outputting 4mA to 20mA, the small output can be 0mA, and the large output cannot exceed 22mA).


    


ONLINE MESSAGE

*Subject:
*E-mail:
Phone:
Company:
*Captcha:

RELATED PRODUCTS

Contact Us

Company Address:

Building 5 and 11, Fuzhou IoT Industrial Park, 

No. 12 Xingye West Road, Mawei District, 

Fuzhou City, Fujian Province, China

Market Cooperation:

Manager Guo: 13959146212


Copyright © 2025 Fujian Aotai Automation Equipment Co., Ltd

This website uses cookies to ensure you get the best experience on our website.