1、 Performance Overview


The NAMUR proximity switch signal in the hazardous area is isolated and converted to output to the safe area. The output mode is open collector output, and inversion selection can also be performed.


The input terminal, output terminal, and power supply terminal are isolated from each other, and have the function of detecting line faults.


输入隔离式安全栅


2、 Technical parameters


Explosion proof grade: [Exia] IIC


Dangerous area allows input signal: NAMUR proximity switch


Active signal trigger point: When the input signal is greater than 2.1m Α, it is indicated as "ON"


When the input signal is less than 1.2m Α, it is indicated as "OFF"


Line fault detection function (LFD): If the input current is less than 50 μ A, it is judged as input disconnection


Input current>6mA, judged as input short circuit


Output signal to safe zone: open collector


Short circuit current: about 8m Α Open circuit voltage: 8V


Current output: ≤ 40mA Short circuit current:<100mA


External input voltage: 40V DC Switching frequency: ≤ 5kHz


Input and output are reversed control settings: K1 is set to the ON side, and the input and output of the corresponding channel are reversed.


K1 is set to side 1, and the input and output of the corresponding channel are in phase.


K2 is set to the ON side and does not include a disconnection alarm output function (no LFD function).


K2 is set to 2 sides and includes a disconnection alarm output function (including LFD function).


Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, testing time 1min)


Insulation resistance: ≥ 100M Ω (between input/output/power supply)


Electromagnetic compatibility: EMC complies with IEC61000-4


Certification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST): Um=250V AC/DC


9. Between 10 terminals: Uo=10.5V, Io=13mA, Po=34mW


ⅡC           ⅡB          ⅡA


Co        1.6μF         11.7μF      52.5μF


Lo        147mH         441mH       1000mH


Power supply: DC 18V~32V (typical value 24V DC)


Power consumption: 24V DC power supply, single collector open circuit output of 0.7W


DC 24V power supply, two collector open circuit outputs 1.0W


Panel indicator light


CH: Output signal status indicator light (red and yellow dual color). When the signal is disconnected or short circuited, it will display in red; When the output circuit is closed, it is displayed in yellow.


Usage environment


Working environment temperature: -20 ℃ to+60 ℃


Allowable relative humidity at work: 10% RH to 90% RH (40 ℃)


Allowable atmospheric pressure during work: 80kPa~106kPa


Allowable ambient temperature during storage and transportation: -40 ℃ to+80 ℃


    


ONLINE MESSAGE

*Subject:
*E-mail:
Phone:
Company:
*Captcha:

RELATED PRODUCTS

Contact Us

Company Address:

Building 5 and 11, Fuzhou IoT Industrial Park, 

No. 12 Xingye West Road, Mawei District, 

Fuzhou City, Fujian Province, China

Market Cooperation:

Manager Guo: 13959146212


Copyright © 2025 Fujian Aotai Automation Equipment Co., Ltd

This website uses cookies to ensure you get the best experience on our website.

Accept Reject