Mr. Guo
Leave a message1、 Overview
The AO8010 series is a universal point control instrument suitable for most applications. The instrument consists of a circuit unit and pole or cable type sensing elements. The sensors can be made of various materials and can be installed as a whole or in a separate type. Used for limit control and alarm.
2、 Working principle
Radio frequency admittance level control technology is a level control technology developed from capacitive level control technology, which has better anti hanging material (the material adhered to the sensor is called hanging material) performance, more reliable operation, more accurate measurement, and wider applicability. The meaning of "conduction" in "radio frequency admittance" is the reciprocal of impedance in electricity, which is composed of resistive, capacitive, and inductive components. "Radio frequency" refers to high frequency, so radio frequency admittance technology can be understood as a method of measuring admittance using high-frequency current.
Road area water meter brings you professional service,the important difference between point RF admittance technology and capacitance technology is the use of three terminal technology and the diversity of measurement parameters. The measurement signal at the center end of the circuit unit is connected to the centerline of the coaxial cable, and then connected to the center end of the sensor. At the same time, the shielding layer of the coaxial cable is suspended at a very small and stable amplitude, but at the same potential, phase, frequency, and no direct electrical relationship with the measurement signal, that is, isolated from each other. Its effect is equivalent to that the measurement signal passes through a gain of "1" and a strong driving ability in-phase amplifier, and the output is connected to the shielding layer of the coaxial cable, and then connected to the shielding layer of the sensor. The ground wire is another independent conductor in the cable. Due to the above-mentioned relationship between the centerline and outer shielding of coaxial cables, there is no potential difference between the two, so no current flows through, that is, no current leaks out from the centerline, which is equivalent to no capacitance or capacitance equal to zero between the two. Therefore, the temperature effect of the cable and the installation of capacitors will not have any impact.
For the problem of hanging materials on the sensor, a new sensor structure is adopted, which is a five layer concentric structure. The sensor structure consists of a central probe rod on the inner layer, a shielding layer in the middle, and grounding installation threads on the outer layer, which are isolated by insulation layers. The situation is the same as with coaxial cables, where there is no potential difference between the center probe and the shielding layer. Even if the impedance of the hanging material on the sensor is small, no current will flow through. Electronic instruments only measure the current from the center of the sensor to the opposite tank wall (ground), because the shielding layer can hinder the current from flowing back to the container wall along the sensor. Therefore, the ground current can only pass through the end of the sensor and the measured material to the opposite container wall.
That is, the U center probe rod=U shielding layer, and the I center probe rod to shielding layer=(U center probe rod - U shielding layer) × YL=0. Although there is a potential difference between the shielding layer and the container wall, and a current flows between them, this current is not measured and does not affect the measurement results. This protects the measuring end from the influence of hanging materials. Only when the material in the container does rise and come into contact with the central probe, can a measured current be formed between the central probe and the ground through the measured material. The instrument detects this current and generates an effective output signal.
Road area water meter brings you professional service,radio frequency admittance technology introduces measurement parameters other than capacitance, especially resistance parameters, which increases the signal-to-noise ratio of instrument measurement signals and significantly improves the resolution, accuracy, and reliability of instruments; The diversity of measurement parameters also greatly expands the reliable application areas of instruments.
Characteristics of RF admittance level meter
Maintenance free: Unlike anti rotation, vibration bar or other mechanical switches, its components will not cause blockage, breakage, damage or wear, and do not require regular maintenance or replacement
Anti hanging material: The Drive shield electrical design allows it to ignore the impact of hanging materials on walls or sensing components, without the need for regular cleaning or repeated debugging
Widely applicable: Process temperature ranges from -183 ℃ to+815 ℃, pressure ranges from vacuum to 100bar
Three color indicator lights: red light - alarm, green light - normal, yellow light - instrument fault, real-time reflection of instrument status
Convenient electrical connection: Dual electrical interface design makes the wiring process safer and more convenient
Strong driving capability: 500 Ω between the center end and the shielding end, and 150 Ω between the shielding end and the ground
Spark protection: Built in 1000V spark protection, surge control, and transient impact control to protect circuit units from damage and ensure normal operation
Easy installation: The instrument can be installed through the threaded port or flange on the tank, and can be installed as a whole or in separate parts, which is simple, convenient, easy to debug, and fast
3、 Scope of application
1. Liquids: conductive liquids and insulating liquids
2. Paddles: Conductive Paddles and Insulated Paddles
3. Particles: grains, plastic sheets, coal, etc
4. Interface: Two liquid interfaces with different medium constants
5. Powder: plastic powder, cement, fly ash, etc
4、 Performance indicators
1. Output: DPDT relay (double pole double throw)
2 Contact Capacity: 250VAC: 1A inductive, 3A non inductive
3. Power supply: 185-255VAC, 50/60Hz 95-135VAC, 50/60Hz 19-29VDC (2W large)
4. Resolution: 0.2pF or less
5. Repeatability:<1mm (0.04 ") (conductive material)<20mm (0.79") (insulating material)
6. Load resistance: 500 Ω between center end and shield end, 150 Ω between shield end and ground
7. Alarm mode: It can be set on-site as HLFS (high-level alarm and fault insurance mode) or LLFS (low-level alarm and fault insurance mode)
8. Alarm light output: red light - level alarm green light - level normal yellow light - instrument malfunction
9. Environmental temperature: -40-~+75 ℃ (-40~167 ℉)
10. Response time:<0.5 seconds
11. Delay: 1-55 seconds (optional)
12. Safety barrier: built-in current limiting and quadruple voltage limiting protection safety barrier
13. Electrostatic spark protection (for sensors): anti surge impact 1000V
14. RF protection (built-in filter): The transmitter circuit has a protective function against RF interference with a power of 5W from other exposed sensing elements, cables, or transmission lines beyond 1.5 meters (59 "), so that the operating point in conductive materials is not affected
15. Probe length: 0.5m (19.7 ") (standard) 0.1m (3.9") to 20m (787.4 ") (optional)
16. Cable length: 5m (197 ") (standard), 0.1 (3.9") to 50m (1968.5 ") (optional)>50m (1968.5" to 100m (3937 ") (consult manufacturer)
17. Electrical interface: Dual M20 × 1.5 (or 3/4 "NPT optional)
18. Process connection: BSPT thread installation (standard, optional NPT), flange installation (optional)
19. Shell protection: Compliant with IP67 protection standard

RELATED
RELATED
RELATED
RELATED
Company Address:
Building 5 and 11, Fuzhou IoT Industrial Park,
No. 12 Xingye West Road, Mawei District,
Fuzhou City, Fujian Province, China
Market Cooperation:
Manager Guo: +8613959146212
Copyright © 2025 Fujian Aotai Automation Equipment Co., Ltd
This website uses cookies to ensure you get the best experience on our website.
Comment
(0)